Outdoor LED indication
Abnormal point
(Failure mode)
LED1
LED2
Overcurrent protection
Once
Goes out
Fin temperature/P.C.
3 times
Goes out
board temperature
overheat
4 times
Goes out
Refrigerant system
Lighting
Lighting
High pressure
protection
Low discharge
temperature
Outdoor fan
Outdoor power
system
Details of abnormal
IPM protection
When overcurrent is detected after
30 seconds of compressor start-up.
Lock protection
When overcurrent is detected within 30
seconds after the compressor gets started.
Fin temperature overheat
When the fin temperature exceeds
protection
during operation.
P.C.boad temperature
When the P.C. board temperature exceeds
overheat protection
°C
70
Discharge temperature
When discharge temperature exceeds
overheat protection
°C
116
HPS protection
When high-pressure is detected with the
high-pressure switch (HPS) during operation.
High pressure protection
When the indoor coil thermistor (TH5)
(Overheat protection)
exceeds 70
When the outdoor heat exchanger thermistor
exceeds 70
Low discharge
When the frequency of the compressor is
temperature protection
kept 80Hz or more and discharge
temperature is kept under 39
than 20 minutes.
Outdoor fan protection
When outdoor fan has stopped within 30
seconds 3-times in a row after outdoor fan
start -up,unit stops.
Outdoor power system
When IPM protection stop or lock
protection stop is continuously
performed 3 times within 1 minute after
the compressor get started, or when
converter protection stop or bus-bar
voltage protection stop is continuously
performed 3 times within 3 minutes after
start-up.
Detecting method
87
°C
during operation.
.
°C
in HEAT mode.
°C
in COOL mode.
°C
for more
Resolución de averías
Check point
• Check the connection of the compressor
connecting wire.
• Check the inverter/ compressor.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Check the outdoor fan motor.
• Check refrigerant circuit and refrigerant
amount.
• Check the LEV.
• Check the outdoor thermistors.
• Check refrigerant circuit and refrigerant
amount.
• Check the stop valve.
• Check refrigerant circuit and refrigerant
amount.
• Check the LEV.
• Check the outdoor fan motor.
• Reconnect compressor connector.
• Check the inverter/ compressor.
• Check the stop valve.
• Check the PAM module.
329