Mitsubishi Electric Mr. SLIM MSZ-FA25VA Technical Manual página 666

Ocultar thumbs Ver también para Mr. SLIM MSZ-FA25VA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Esquemas frigorífi cos
SUZ-KA25VA SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH
MAX. REFRIGERANT PIPING LENGTH
Models
SUZ-KA25VA
SUZ-KA35VA
SUZ-KA25VAH
SUZ-KA35VAH
MAX. HEIGHT DIFFERENCE
Indoor
unit
Max. Height
difference 12m
Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Models
SUZ-KA25VA
SUZ-KA25VAH
SUZ-KA35VA
SUZ-KA35VAH
666
Refrigerant piping
Max. length : m
A
20
Refrigerant Piping
Max. length
Outdoor unit
precharged
5m
6m
900
0
0
0
0
1,050
Piping size O.D : mm
Gas
Liquid
6.35
9.52
A
Outdoor unit
Refrigerant piping length (one way)
7m
8m
9m
10m
0
90
120
150
0
120
150
90
Calculation : Xg=30g/mo(Refrigerant piping length(m) - 5)
11m
12m
13m
14m
180
270
210
240
180
210
240
270
15m
20m
300
450
300
450

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mr. slim msz-fa35vaMr. slim muz-fa25vaMr. slim muz-fa35vaMr. slim msz-ga22vaMr. slim msz-ga25vaMr. slim msz-ga35va ... Mostrar todo

Tabla de contenido