Check The Application Conditions - SICK HL18 Instrucciones De Uso

Ocultar thumbs Ver también para HL18:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 106
7.2

Check the application conditions

8017290.1A15 / 2020-12-14 | SICK
Subject to change without notice
Optimized alignment can be achieved and verified by using the signal strength light bar
located on the back of the sensor. The LEDs on the light bar will illuminate correspond‐
ing to the signal strength light received by the sensor. When no or only red LEDs are
illuminated, the sensor is receiving no or too little signal to switch the output. The first
yellow LED will illuminate at the minimum switching threshold and the green LEDs will
continue to illuminate as the received light increases.
100 %
100 %
0 %
Figure 2: Signal strength light bar during alignment
Sensing range
Adjust the distance between the sensor and the reflector according to the correspond‐
ing diagram (x = sensing range, y = operating reserve).
NOTE
Note the minimum sensing range between sensor and reflector depending on the
reflector.
Operating reserve
100
10
6
1
0
1
2
3
4
(3.28)
(6.56)
(9.84)
(13.12)
Figure 3: HL18: Operating reserve
Reflector PL80A
1
Reflector PL40A
2
Reflective tape IREF6000 (REF-
6
IRF-56)
100 %
0 %
0 %
Operating reserve
10
2
1
1
5
6
7
0
(16.40)
(19.67)
(22.97)
Distance in m (feet)
Figure 4: HL18G/HL18T: Operating reserve
1
2
3
5
6
COMMISSIONING
100 %
100 %
0 %
0 %
5
3
2
1
6
0.5
1
1.5
2
2.5
(1.64)
(3.28)
(4.92)
(6.56)
(8.20)
(9.84)
Distance in m (feet)
Reflector PL80A
Reflector PL40A
Reflector P250F
Reflective tape REF-AC1000
Reflector PL41F
7
3
3.5
(11.48)
17

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hl18lHl18gHl18t

Tabla de contenido