Code
Alarm
ALH03
High humidity/
temp. (limit
probe)
ALW01
Foam warning
ALT01
Maintenance
request
ALW02
Boiler full
ALA04
Conductivity
meter
ALR01
Retain memory
error
ALP01-4
Wireless probe
1-4 offl ine
ALM01
Model not set
ALN01-20
Network: prob-
lem with unit
1-20
ALP05-8
Warning: low
battery level on
wireless probe
1-4
ALA05
Main wireless
probes
Wireless probes
ALA06
Limit wireless
probes
Wireless probes
ALP09
High
boiler temper-
ature
ALA07-09
Overload
on fan 1-3
ALP10-12
Flue gas probe
1-3 broken
ALP13-15
Flue gas
temperature 1-3
warning
ALP16-18
Flue gas temper-
ature 1-3 alarm
ALA10-12
Burner 1-3 no
fl ame alarm
ALA13
Frost protection
check compo-
nents
ALA20-22
Burner 1-3 speed
error
ALP24
No secondary
model
20
Cause
High humidity at outlet
Entrainment of foam in the boiler
during boiling
Planned maintenance reminder
Boiler full of water to the high level
sensor on the cover, without humidifi -
cation request
Conductivity meter not connected
Problem in the electronic controller
No communication with probe 1-4
Model not set
Network unit alarm
(see the unit specifi ed for details)
Battery discharged on wireless probe
1-4
All the main wireless probes are not
working
All the limit wireless probes are not
working
The boiler temperature read by the
NTC probe is too high > 110°C
Thermostat activated due to abnor-
mal overheating of the boiler from
operation without water
fl ue gas temperature probe 1-3
broken. NTC probe for measuring the
fl ue gas temperature not connected
or not working
fl ue gas temperature probe 1-warning
alarm > 175 °C. Excessively high fl ue
gas temperature, boiler full of scale
fl ue gas temperature probe 1-3 alarm
> 180 °C. Excessively high fl ue gas
temperature, boiler full of scale
ignition failure on burner 1-3. No
fl ame with production request.
with the unit on, there is no steam
production or water preheating;
fl ue gas outlet or air intake blocked;
gas shut-off valve closed, burner and/
or controller malfunction;
no gas supply
temperature below 5°C
drain water using the pump to pro-
tect components
on the humidifi er
Speed fault on burner 1-3
no model set
for Secondary unit.
Possible solution
Check the operation of the outlet limit probe
• The entrainment of foam is generally due to
the presence of surfactants in the water (lubri-
cants, solvents, detergents, water treatment or
softening agents) or an excessive concentra-
tion of dissolved salts.
• Purge the feedwater lines
• Clean the boiler
Stop the unit and carry out complete mainte-
nance on the humidifi er, then reset the "boiler
operating hours" counter (screen Ea07)
• Check the fi ll valve for leaks;
• Check whether the high level sensor is dirty;
• Check that there is no condensate return
along the steam hose;
Check the connection of the conductivity meter
for measuring feedwater conductivity
Replace the controller
Check binding between probe and access
point, check the battery. Check the probe signal
level.
Set a model
• Carry out the checks according to the alarm
• displayed on the unit in question
Check battery charge, replace if necessary;
Check probe connections and binding to the
access point
Check probe connections and binding to the
access point
• Check that there is water in the boiler;
• check that the level sensor is working and/
or clean it
• stop the unit and carry out
• complete maintenance on the boiler
• Check the probe connections and/or oper-
ation
• of the probe
• switch the unit off , clean the heat exchanger,
• check burner calibration.
• switch the unit off , clean the heat exchanger,
• check burner calibration
• check the gas pressure and that the gas shut-
off valve is open;
• make sure that the air intake is not blocked;
• check the fan power connection;
• check operation of the brushless fan, the fl ue
gas outlet and air intake;
• burner fl ame malfunction;
• check the connections between the fl ame
control board and the burner, and between
the electrical panel and the fl ame control;
• check the connections between the unit
controller and the intermediate terminal block
in the electrical panel
check the temperature inside and outside of the
humidifi er. Increase the temperature inside the
humidifi er by fi tting additional heaters where
necessary.
check the electrical connections between the
control board and the fan; if necessary remove
the brushless fan and check its operation.
Set the model on the Secondary unit
Reset
Action
Automatic
Signal
only
Automatic
Signal
only
Automatic
Signal
(reset operating
only Unit
hours)
shutdown
in relation
to water
hardness.
Automatic
Signal
only
Manual
Stop pro-
duction
Automatic
Signal
only
Automatic
Signal
only
Automatic
Stop pro-
when the mod-
duction
el is selected
Automatic
Signal
only
Automatic
Signal
only
Stop - auto-
Stop pro-
matic
duction
Stop - auto-
Stop pro-
matic
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction
Stop with
Stop pro-
manual reset
duction