Description; Scope Of Delivery - WIKA ACS-10 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2. Design and function

2.2 Description

With the calibration system for SF₆ density measuring instruments, model ACS-10,
qualified personnel can recalibrate gas density measuring instruments e.g. in the field,
as part of the receiving inspection or during commissioning of an electrical system. A
recalibration generally refers to a functional check of a leakage detection system.
Model ACS-10 can apply pressure to a leakage detection system by means of the
integrated compressor and then slowly release the pressure. Meanwhile, the switching
EN
accuracy, hysteresis and contact resistance of the mechanical switch are measured.
This ensures that the gas density measuring instrument functions properly and meets
the operator's desired requirements.
The model ACS-10 is equipped with an integrated gas storage vessel as well as
a compressor. With these components and high-accuracy sensors for pressure
and temperature measurement, the calibration system can be used as a reference
instrument for a recalibration. Common gas density monitors and gas density switches
with up to five change-over contacts as well as gas density indicators can be subjected
to a functional test.

2.3 Scope of delivery

Main case
Connection kit
Adapter DN8 female to quick coupling
Adapter DN20 female to quick coupling
Hose pack 4 m [13.1"]
16-core connection cable for gas density monitor and switch, for up to 5 change-over
contacts
Power supply unit with connector adapters for USA, China and the UK
Documents
Adapter for gas density monitor with connectors as cable socket
Optional accessories case
Freely configurable for the optional accessories
Cross-check scope of delivery with delivery note.
52
WIKA Betriebsanleitung Kalibriersystem, Typ ACS-10

Publicidad

Tabla de contenido
loading

Tabla de contenido