Programming of the device
Selection of the threshold of switch-on and switch-off ventilation
It is possible to program the threshold for enabling and disabling the ventilation.
• Selection the threshold for disabling ventilation
The FAN LED is on, with fixed light indicates this phase of programming.
With ← and → keys select the value of temperature indicated on display.
Interval of programming: from -25°C up to (enabling threshold -1°C)
Confirm with ENTER.
• Selection the threshold for enabling ventilation
The FAN LED is on, with flashing light indicates this phase of programming.
With ← and → keys select the value of temperature indicated on display.
Interval of programming: from (disabling threshold +1°C) up to 200°C
Confirm with ENTER.
Selection of the alarm and trip threshold
This setting starts to program from the channel number 1.
The ALARM LED ON indicates the programming of the alarm:
With ← and → keys select the value of temperature
Interval of programming: from -25°C up to (trip threshold -1°C)
Confirm with ENTER.
The TRIP LED ON indicates the programming phase of the tripping threshold.
With ← and → keys select the value of temperature
Interval of programming: from (alarm threshold +1°C) up to 200°C.
Confirm with ENTER.
Repeat the same operation for the successive channels.
Selection of address network identification for the communication of the serial
port (MODBUS-RTU protocol)
This setting is significant only for eDTI model.
This setting is indicated on displays with:
• value to set on T1-T2 display
• ID on T3-T4 display.
With ← and → keys select the number choice
The range for accepted value is from 1 to 247.
Confirm with ENTER.
Modbus setting
Setting address MODBUS network
10
NOTE
TEMPERATURE MONITORING UNIT DTI AND EDTI