Programming of the device
Selection of the linked channel with the analogue output
This setting is significant only for eDTI model.
This setting is indicated on displays with:
• AN on T1-T2 display
• the linked measure channel on T3-T4 display: CH 1/2/3/4 for the 1/2/3/4
measure channel, ALL to link the measure channel with the higher temperature.
With ← and → keys to select the options.
Confirm with ENTER.
Link channel setting
Channel with higher temperature
Measure channel CH 1
Measure channel CH 2
Measure channel CH 3
Measure channel CH 4
Configuration output signal
This setting is significant only for eDTI model.
In this phase it's possible to define the type of signal of analogue output as 0-20
mA or 4-20 mA.
This setting is indicated on displays with:
AN0 -20 to set the output as 0-20mA or (0 mA = -30°C; 20 mA = 200°C)
AN4 -20 to set the output as 4-20 mA or (4 mA = -30°C; 20 mA = 200°C)
With ← and → keys select the options.
Confirm with ENTER.
Analogue signal setting
Output proportional 0 - 20 mA
Output proportional 4 - 20 mA
12
NOTE
NOTE
TEMPERATURE MONITORING UNIT DTI AND EDTI
T1-T2 display
AN
AN
AN
AN
AN
The maximum load for analogue output
is 400 Ω.