Programming of the device
Configuration diagnostic probes
This function allows to enable or to disable the control on the probes. This fun-
ctionality controls the variation of the temperature in a defined time. A flag raise
if this variation is higher than a set value.
FDC setting
FDC mode disabled
FDC mode enabled
It's necessary to indicate the maximum variation temperature:
• FDC: min 5°C or max 30°C
and after the time in which to do the control:
• FDC: min 10" or max 90" (time in seconds)
The →+ key is used to increase the values while the ←- key to decrease.
Confirm with ENTER.
Temperature configuration FDC
Min °C
Max °C
Time configuration FDC
Min in seconds
Max in seconds
Exit from the programming phase
Press the SET key or wait for about 8 seconds without to press any key to come
out of the programming phase.
T1-T2 display
FDC
FDC
T1-T2 display
FDC
FDC
T1-T2 display
FDC
FDC
T3-T4 display
Off
ON
T3-T4 display
-5°
30°
T3-T4 display
10''
90''
13