4.5.3 
Operation floor drying
(fig. 22/a)
The. operation. floor. drying. keeps. the. floor.
at. a. pre-established. temperature. profile.
and. it. is. activated only for those systems 
combined  with  the  mixed  zone  card 
ZONA MIX code 8092275/76..
The. temperature. profiles. can. be. selected.
by. means. of. the. installer. parameter. PAR.
43:.
0.=.Not.activated.function
1.=.Curve.setting.A
2.=.Curve.setting.B
3.=.Curve.setting.A.+.B
The. turning. off. of. . the. function. happens.
clicking. on. the. button. OFF. (return. of. PAR.
43. to. the. value. 0). or. automatically. at. the.
[TVw]
55
50
45
40
35
30
25
20
0
1
X
1
end.of.the.function..
The.set.of.the.mixed.zone.follows.the.deve-
lopment.of.the.selected.curve.and.reaches.
a.maximum.of.55°C..
During. the. function. all. the. other. heating.
demands. are. ignored. (heating,. sanitary,.
antifreeze.and.chimney.sweep)..
During. the. functioning. the. display. shows.
the. remaining. days. for. the. completion. of.
the.function.(example.mains.digits.-15.=.15.
days. lack. to. the. end. of. the.
diagram.fig..22/a.reports.the.development.
of.the.curve.
ATTENTION:
-   Observe  the  relevant  standards  and 
regulations of the floor manufacturer!
-   Proper  functioning  is  ensured  only 
when  the  plant  is  correctly  installed 
(hydraulic  system,  electrical  installa-
5
7
1
5
A
A + B
TVw.
Flow.temperature.setpoint
Tag.
Period.in.days
x.
Start.day
A.
Functional.heating
B.
Floor.curing.heating
tion, settings)! If not observed, the floor 
might get damaged!
4.6 
FUNCTIONING ANOMALIES
When. there. is. a. functioning. anomaly,. an.
alarm.appears.on.the.display.and the blue 
luminous bar becomes red.
Descriptions.of.the.anomalies.with.relative.
function)..
The.
alarms.and.solutions.are.given.below:
–. LOW  WATER  PRESSURE  ANOMALY 
ALARM 02 (fig. 23/1)
.
If.the.pressure.detected.by.the.transdu-
cer.is.lower.than.0.5.bar,.the.boiler.stops.
and. the. display. shows. the. . alarm. "ALL.
02".. Proceed. with. the. pressure. resto-
ration. until. the. pressure. indicated. by.
transducer.is.between.1.and.1.5.bar.
10
15
B
18
[Tag
]
25
Fig..22/a
ES
PT
ENG
105