Descargar Imprimir esta página

Sime MURELLE HE 35 R ErP Manual De Instrucciones página 88

Ocultar thumbs Ver también para MURELLE HE 35 R ErP:

Publicidad

Idiomas disponibles

Idiomas disponibles

2.6 
POSITIONING THE 
OUTLET TERMINALS (fig. 7)
The. outlet. terminals. for. forced-draught.
appliances. may. be. located. in. the. external.
perimeter.walls.of.the.building..
To. provide. some. indications. of. possible.
solutions,. Table  3. gives. the. minimum.
distances.to.be.observed,.with.reference.to.
the.type.of.building.shown.in.fig..7.
2.7 
ELECTRICAL CONNECTION
The. boiler. is. supplied. with. an. electric.
cable.. Should. this. require. replacement,. it.
must.be.purchased.exclusively.from.SIME..
88
The. electric. power. supply. to. the. boiler.
must.be.230V.-.50Hz.single-phase.through.
a. fused. main. switch,. with. at. least. 3. mm.
spacing.between.contacts..
Respect. the. L. and. N. polarities. and. the.
earth.connection.
NOTE: SIME declines all responsibility for 
injury  or  damage  to  persons,  animals  or 
things,  resulting  from  the  failure  to  pro-
vide for proper earthing of the appliance.
2.7.1 
Chronothermostat  
connection
Connect.the.chronothermostat.as.indicated.
TABLE 3
Siting.of.terminal.
. . .
A. -. below.openable.window.
B. -. below.ventilation.opening.
C. -. below.eaves.
D. -. below.balcony.(1).
E. -. from.adjacent.window.
F. -. from.adjacent.ventilation.opening.
G. -. from.horizontal.or.vertical.soil.or.drain.pipes.(2).
H. -. from.corner.of.building.
I. -. from.recess.in.building.
L. -. from.ground.level.or.other.treadable.surface.
M. -. between.two.terminals.set.vertically.
N. -. between.two.terminals.set.horizontally.
O. -. from.a.surface.facing.without.openings.or.terminals.
P. -. as.above.but.with.openings.and.terminals.
1). Terminals.below.a.practicable.balcony.must.be.located.in.such.
a.way.that.the.total.path.of.the.smoke.from.its.outlet.point.from.
the.terminal.to.its.outlet.point.from.the.external.perimeter.of.the.
balcony,.including.the.height.of.possible.railings,.is.not.less.than.
2000.mm.
2). When.siting.terminals,.where.materials.that.may.be.subject.to.
the.action.of.the.combustion.products..are.present.in.the.vicinity,.
e.g.,.eaves,.gutters.and.downspouts.painted.or.made.of.plastic.
material,.projecting.timberwork,.etc.,.distances.of.not.less.than.
1500.mm.must.be.adopted,.unless.adequate.shielding.is.provi-
ded.to.guard.these.materials.
in.the.boiler.electrical.diagram.(see fig. 11) 
after.having.removed.the.existing.bridge..
The.chronothermostat.to.be.used.must.be.
of. a. class. conforming. to. the. standard. EN.
607301.(clean.electrical.contact).
2.7.2 
Remote control 
SIME HOME
connection (optional)
The. boiler. is. designed. for. connection. to. a.
remote. control. unit. SIME.HOME,. supplied.
on.request.(code.8092280/81)..
The.remote.control.unit.SIME.HOME.allows.
for.complete.remote.control.of.the.boiler..
The. boiler. display. will. show. the. following.
Appliances.from.7.to.35.kW
(distances.in.mm)
600
600
300
300
400
600
300
300
300
2500
1500
1000
2000
3000
Fig..7

Publicidad

loading