INSTALLATION
The.boiler.must.be.installed.in.a.fixed.loca-
tion. and. only. by. specialized. and. qualified.
firms. in. compliance. with. all. instructions.
contained. in. this. manual.. Furthermore,.
the.installation.must.be.in.accordance.with.
current.standards.and.regulations..
WARNING:  Before  installing  the  boiler, 
the  installer  MUST  make  sure  that  the 
wall can support the weight.
2.1 
INSTALLATION
2.1.1   Single boiler (fig. 4)
–..Boilers. can. be. installed. in. all. domestic.
environments. without. any. whatsoever.
limit.in.terms.of.location.and.comburent.
air.supply.
–..These. boilers. can. also. be. installed. in.
partially.covered.areas,.as.per.EN.15502,.
with. a. maximum. ambient. temperature.
of.60°C.and.a.minimum.ambient.tempe-
rature. of. -5°C.. It. is. generally. advisable.
Single installation
with kit optional code 8101557
WARNING: 
-   I t  is  mandatory  to  arrange  the  thermal 
system with the hydraulic separator.
-   W hen  replacing  one  or  more  boilers  in 
existing  plants,  it  is  advisable  to  install 
a heat exchanger to separate the boiler 
circuit  from  the  secondary  circuits.  See 
the pressure curve for the boiler supply 
shown in figure 14.
ON
1 2 3
80
to. install. the. boilers. below. weathered.
roofs,. on. the. balcony. or. in. a. protected.
niche,.to.protect.them.from.exposure.to.
weathering.agents.(rain,.hail.and.snow)..
All.boilers.provide.a.standard.antifreeze.
function..
A.single.function.compensator.kit.is.availa-
ble.upon.request:.cod...8101557.
The.kit.is.for.use.on.an.accumulating.boiler.
with. capacity. equal. to. or. greater. than. 80.
litres.
2.1.2   Sequence/cascade boilers 
(fig. 4/a)
In.the.event.of.sequence/cascade.installa-
tion,.you.must.modify.for.every.single.boi-
ler.of.the.main.unit.the.following.installing.
parameters:
-.. P AR 1 = 4.
. (for.G20.NATURAL.GAS.boilers)
-.. P AR 1 = 12.
M2
M
x 2
DIP SWITCH
GESTIONE IN CASCATA
CASCADE MANAGEMENT
. (for.G31.PROPANE.boilers)
Refer. to. section. 3.3. to. access. the.
INSTALLER.PARAMETERS.section.
ATTENTION:  In  sequence/cascade  instal-
lations,  it  is  mandatory  to  arrange  the 
thermal  system  with  the  hydraulic  sepa-
rator and safety devices.
The. boiler. is. provided. with. the. board.
RS-485. that. permits. to. manage. up. to. 8.
boilers. in. cascade. and. communication. in.
MODBUS...The.board.is.placed.on.the.back.
of.the.control.panel.
Access. the. board. and. chose. the. desired.
operating.mode.(CASCADE.or.MODBUS).by.
selecting. the. DIP. SWITCH. of. the. board. as.
indicated.in.figure.4/a.
CASCADE mode (fig. 4/b)
Electrically. connect. all. the. boilers. that.
form.the.modular.cascade.thermal.system.
and. set. installer. parameters. PAR. 15. on.
every.single.boiler.as.indicated.in.fig..4/b.
MURELLE HE 35 R
450
340
R3
123
R
170
140
330
60
DIP SWITCH
ON
GESTIONE IN CASCATA
CHIAVE
POLARIZATION
CASCADE MANAGEMENT
1 2 3
CN10
DIP SWITCH
ON
GESTIONE IN MODBUS
MODBUS MANAGEMENT
1 2 3
MURELLE HE 35 R UK
450
C.H..flow
M.
.
R.2".(UNI-ISO.7/1).
C.H..return
R.
.
R.2".(UNI-ISO.7/1)..
M2. D.H.W..tank.flow
.
G.3/4".(UNI-ISO.228/1).
R3. D.H.W..tank.return
.
G.3/4".(UNI-ISO.228/1).
M2
R3
M
R
170
140
330
60
Fig..4
ON
1 2 3
Fig..4/a
340
123
DI
GE
M

Publicidad

loading