MODBUS mode (fig. 4/c)
The.RS-485.board.can.be.used.for.MODBUS.
communication.of.every.MURELLE HE 35 R 
ErP boiler..
In.this.case,.proceed.as.follows:
COMUNICAZIONE MODBUS
MODBUS COMMUNICATION
GND
+
GND
+
TABELLA PAR 17 INST/ Tab. PAR 17 INST
PAR 17 INST
Par 17 INST
82
-. Set.the.DIP.SWITCH.of.the.RS-485.board.
and.the.PAR.16.as.indicated.in.the.figure..
-. Choose. the. communication. configura-
tion.suited.to.the.MODBUS.network.(PAR.
17. INST). according. to. Table  PAR  17 
INST.
DIP SWITCH
CONNETTORE
CABLATO CN10
ON
(cod. 6319165)
WIRED CONNECTOR CN10
1 2
3
(code 6319165)
SCHEDINO RS-485
RS-485 BOARD
/ BOILER BOARD
SCHEDA CALDAIA
Baud Rate
Baud Rate
1
1200
2
1200
3
1200
4
1200
5
1200
6
1200
7
2400
8
2400
9
2400
10
2400
11
2400
12
2400
13
4800
14
4800
15
4800
16
4800
17
4800
18
4800
19
9600
20
9600
21
9600
22
9600
23
9600
24
9600
25
19200
26
19200
27
19200
28
19200
29
19200
30
19200
INSTALLER PARAMETER SETTING:
PAR 16  
.
.
.
..
.
.
PAR 17  
.
.
.
..
.
.
.
.
.
ATTENTION: Upon  setting  the  parameters,  we 
recommend turning the boiler off and then back 
on again.
N° Bit Dati
Parità
No. Data Bit
Parity
8
No
8
No
8
Pari /
Even
Pari /
Even
8
8
Dispari /
Odd
Dispari /
8
Odd
8
No
8
No
Pari /
Even
8
Pari /
Even
8
Dispari /
8
Odd
8
Dispari /
Odd
8
No
8
No
Pari /
8
Even
Pari /
Even
8
Dispari /
Odd
8
Dispari /
Odd
8
8
No
8
No
Pari /
Even
8
Pari /
Even
8
Dispari /
8
Odd
Dispari /
Odd
8
8
No
8
No
Pari /
Even
8
Pari /
Even
8
Dispari /
Odd
8
Dispari /
Odd
8
CASCADE+MODBUS mode (fig. 4/d)
This. mode. allows. for. MODBUS. communi-
cation.of.at.least.two.boilers.in.cascade.and.
is.performed.by.requesting.another.RS-485.
board.provided.in.the.kit.code.8092248...
MODBUS ADDRESS
--.=.Not.enabled
1...31.=.Slave.from.1.to.31
(ATTENTION:  Avoid  calling  the 
boiler  with  the  same  number 
assigned to either appliances)
MODBUS CONFIGURATION
--.=.Not.enabled
1...30.=.Default.value:.25
(See.Table PAR 17 INST)
Bit di Stop
Stop Bit
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
Fig..4/c