(ATTENTION: the total length of each pipe 
should  not  exceed  25  m,  even  if  the  total 
loss  is  below  the  maximum  applicable 
loss.)
The.exhaust.pipe.can.be.connected.to.exi-
sting. chimneys.. When. the. boiler. works. at.
low.temperature.is.possible.to.use.normal.
chimneys.at.the.following.conditions:
–. The.chimney.must.not.be.used.by.other.
boilers..
–. The. inside. of. the. chimney. must. be. pro-
tected. from. direct. contact. with. the. boi-
ler.condensation...Combustion.products.
must. be. conveyed. with. a. flexible. piping.
or.rigid.plastic.pipes.with.a.diameter.of.
about. 100-150. mm. providing. so. to. the.
condensation. siphoned. drainage. at. the.
end.of.the.pipe..The.useful.height.of.the.
siphon.must.be.at.least.150.mm.
For. the. accessories. load. loss. refer. to. .
Table 1.
86
2.5 
INSTALLATION OF SEPARATE 
DUCTS TYPE C (ø 80)
This. type. of. exhaust. is. made. with. ø. 80.
polypropylene.accessories.and.without.the.
use. of. gasket. or. sealant. in. type. C. instal-
lation..
The  maximum  overall  length,  resul-
ting  from  the  sum  of  all  the  suction  and 
discharge  pipes,  is  determined  by  the 
load losses of the single connected acces-
sories and should not exceed 15 mm H
(ATTENTION: the total length of each pipe 
should  not  exceed  25  m,  even  if  the  total 
loss  is  below  the  maximum  applicable 
loss.)
See.Table 2.for.information.on.the.load.los-
ses.of.single.accessories.and.the.example.
of.fig..6/a.for.information.on.how.to.calcu-
late.load.losses.
TABLE 1
Accessory.ø.80.
..
90°.MF.polypropylene.curve.
45°.MF.polypropylene.curve.
Polypropylene.extension.L..1000.(horizontal).
Polypropylene.extension.L..1000.(vertical).
Wall.exhaust.terminal.
Roof.exit.terminal..L..1381.
.Extension.L..250.with.connection.
WARNING:  Before  installing  accessories,  lubricate  the 
internal  part  of  gaskets  with  silicon-based  products. 
Avoid using oils and greases. 
KEY
...1.. . 90°.MF.polypropylene.curve.(6.pcs.).code.8077450
. 2.a. Polypropylene.extension.L..1000.(6.pcs.).code.8077351
. 2.b. Polypropylene.extension.L..500.(6.pcs.).code..8077350
. 3.. Hinged.tile.code.8091300
.
4.. Roof.terminal.kit.L..1381.code.8091204
. 5.. Extension.L..250.
. 6.. 45°.MF.polypropylene.curve.(6.pcs.).code.8077451
. 7.. Exhaust.terminal.code.8089501
. 8.. Internal-external.ring.nut.kit.code.8091500
. 1 1.. Rubber.gasket.ø.80.(supplied.as.standard).
2.5.1 
Separate ducts kit (fig. 6/b)
The. diagrams. of. figure. 6/b. show. a. few.
examples. of. the. permitted. exhausts. con-
figurations.
2.5.2 
Connection to existing flues
The. ø. 80. exhaust. pipe. can. also. be. con-
nected. to. existing. flues.. When. the. boiler.
runs. at. low. temperature,. it. is. possible. to.
use.standard.flues.provided.that:
O 
-.. The.flue.is.not.be.used.by.other.boilers.
2
-...The. interior. of. the. flue. is. protected. to.
prevent. a. direct. contact. with. conden-
sation. from. the. boiler.. The. products. of.
combustion.must.be.conveyed.through.a.
flexible. or. rigid. plastic. pipe. around. 100.
to. 150. mm. in. diameter,. and. condensa-
tion. must. be. siphoned. off. at. the. foot. of.
the.pipe..The.usable.height.of.the.water.
trap.must.be.at.least.150.mm.
Load.loss.
(mm.H
with.connection.
code.6296513
O)
2
0,40
0,25
0,25
0,25
0,50
0,20
---
Fig..6