ASSEMBLY
OVERVIEW
See Figure 3.
The transfer switch allows you to safely use generator
power through existing electrical wiring. Once the
transfer switch is installed, you can use the circuit
selectors to determine the power source for each circuit
connected to the switch. The switch will not allow you to
use generator and utility power at the same time.
CAUTION
be 240VAC. This switch is not compatible with
120VAC generator output voltage.
DANGER
operating a generator, make sure it is located in
an open, outdoor area, at least 20 ft. (6 m.) from
occupied spaces with exhaust pointed away.
INSTALLATION
MOUNTING THE TRANSFER SWITCH
See Figures 4 - 9.
Always mount the transfer switch indoors and no farther
than 16 inches away from the load center. When choosing
a suitable location consider the layout of the room, user
convenience, and the proximity to the load center.
DANGER
with care during installation. Never mount or wire
a damaged transfer switch. A damaged transfer
switch could malfunction and create electrical
hazards that could result in death, serious injury,
and equipment failure.
l Turn the main circuit breaker in the load center to the
OFF position.
NOTE: Power should remain off during installation. Take
all appropriate actions for prolonged power outages
including actions that will preserve food and protect
sensitive equipment.
Generator output voltage must
Asphyxiation hazard. When
Handle
transfer
FIG. 3
C
B
A
A - Generator
B - Power Inlet Box
C - Junction Box
D - Transfer Switch
E - Load Center (Utility)
DANGER
in the load center to the OFF position, does not shut
off power on the utility side of the main breaker. The
wires on the utility side are still live and contact with
them can result in serious injury and death.
l Select a suitable location for the transfer switch
approximately 16 in. away from the load center. Mark
switches
the location.
FIG. 4
(40,6 cm)
E
D
Turning the main circuit breaker
16 in.
16 in.
(40,6 cm)
English | 9