Connecting Pressurized Steam To An Ultimatesam Distributor; Connecting Atmospheric Steam To A Bottom-Feed Ultimatesam Distributor - Carel ultimateSAM Manual Del Usuario

Ocultar thumbs Ver también para ultimateSAM:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ENG
Nota: for valve types "*****FH*0*" the actuator is included in the
valve kit, so the code (SAKAE00200) indicated above is to be used
when ordering a spare actuator only.
Pneumatic Actuator Selection
Valve Size
*****F0*0*
*****H0*0*
SAKV0**A*0
n/a
SAKV0**B*0
SAKV0**C*0
n/a
SAKV0**D*0
SAKV0**E*0
SAKV0**F*0
SAKV0**G*0
SAKV0**H*0
n/a
SAKV0**I*0
n/a
SAKV0**J*0
SAKV0**K*0
n/a
SAKV0**L*0
n/a
For weights and dimensions of the actuators, see see the "Technical
specifi cations". This section also provides information regarding control
signal requirements for the actuators.
5.4 Connecting pressurized steam to an
ultimateSAM distributor
1
3
2
4
Fig. 5.a
For threaded control valves, SAKV****U*, with an optional fi tting kit,
SAKR****U*, attach the fi ttings to the valve as shown in fi gure 4.a.
Attach the  optional actuator, SAKA******, to the  control valve.
Connect the valve/actuator assembly to the inlet adapter on the
distributor header. For optimal performance, the valve should be
attached directly to the inlet. If a connecting pipe is needed between
the valve and inlet, the length of the pipe should be as short as
possible. The actuator should be oriented in the upright position. See
fi gures 1.k and 4.c.
Assemble the fi ttings and components included in the optional 
trap and  strainer kit, SAKT******, and attach the trap assembly
to the valve. For steam operation, strainers should be installed in the
horizontal position, although it is acceptable to mount the strainer
pointing downward. The horizontal position prevents water from
collecting in the bonnet thereby reducing the risk of airborne droplets.
Fig. 5.c
"ultimateSAM - user" +0300070ES - rel. 1.0 - 23.05.2013
Material, Pressure, Region Codes
*****00*U*
*****0H*U*
SAKAP001U0
n/a
SAKAP001U0
SAKAP002U0
SAKAP001U0
SAKAP003U0
SAKAP002U0
SAKAP003U0
SAKAP003U0
n/a
n/a
n/a
3
4
Fig. 5.b
Nota: The "P"
drains shown
above are not
provided as part of the
ultimateSAM system.
5.5 Connecting atmospheric steam to a bottom-
feed ultimateSAM distributor
Tab. 5.g
1
2
Nota: The adapters and steam hoses shown above are available as
options. The "P" drains are not provided as part of the ultimateSAM
system.
The distributor should be positioned at a height above the humidifi er
so that condensate drains back to the humidifi er.
1.
If using fl exible steam hose to connect the distributor to the humidifi er,
a minimum angle of 20° should be allowed from humidifi er outlet
to distributor inlet.
2.
If using rigid steam pipe to connect the distributor to the humidifi er,
the pipe should have a minimum 1% grade (~1 cm per meter,
~1/8" per foot) to allow for proper drainage back to the humidifi er.
If using a dual or quad inlet adapter, the 150mm (6") inlet extension is
recommended. Install the extension inlet to the header. Connect the
steam hose from the humidifi er such that inlet adapter, making sure
that the hose is sloped so that most of the condensate returns to the
humidifi er.
20
Fig. 5.d
20° min.
Fig. 5.e