Mounting Sab/Sat Models - Carel ultimateSAM Manual Del Usuario

Ocultar thumbs Ver también para ultimateSAM:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1.7.1

Mounting SAB/SAT models

NOT AVAILABLE ON THE NORTH AMERICAN MARKET
Fig. 1.o
NORTH AMERICAN MARKET ONLY
Fig. 1.p
Fig. 1.q
Nota: The inlet adapter, control valve, actuator, trap, and strainer
shown above are available as options. The "P" drains are not
provided as part of the ultimateSAM system.
Face-off
Attach any optional inlet and/or drain connections to the distributor
that will need to pass through the wall of the duct. (Fig.1.o) See section
2 for information in inlet connections. See section 3 for information on
drain connections.
Unless the distributor has been assembled inside the duct or AHU,
cut an opening in the duct through which the distributor can be
inserted. The opening can be in either the side or bottom of the duct,
depending on accessibility. (Fig.1.o)
Cut out any additional openings in the duct or AHU as needed for the
inlet and/or drain connections.
If desired, shim the inlet side of the distributor so that condensate in
the header with fl ow toward the drain pipe. A 1% grade (~1 cm per
meter, ~1/8" per foot) is suggested.
Secure the bottom pedestals to the duct.
Secure the top corners of the side channels to the walls of the duct
or AHU.
Face off all sides of the duct, as necessary, so that air fl ow is directed
through the uprights as much as possible. (Fig.1.p)
Mounting SA0 (single-pipe) versions)
Installation with manifold outside the duct
Follow the installation procedure described below:
1.
assemble the SA0 steam distributor (see paragraph 1.4.2 Assembling the
frame, SA0 versions);
2.
apply the drilling template to the duct where the steam distributor will
be installed;
3.
drill the required holes;
4.
insert the gasket and rest it against the support fl ange;
5.
insert the fastening screws to secure the support fl ange;
6.
place the upright in the 100 mm opening made in the duct;
7.
fasten the support fl ange screws to 7-8Nm (5-6ft), using the fastening
elements supplied;
8.
If necessary, secure the end of the upright.
11