Solution and Troubleshooting
Protection
Description and
Fault Display
Electronic motor
When the times given by the
overload
programmed thermal class curves
exceed the limit.
E05
(LED Overload)
Flashing
Start timeout
When the starting time is longer than
during current
the time set in the acceleration ramp
limit starting
trimpot.
Active only with current limit starting.
E62
(LED Fault)
Flashes twice
(LED Ready)
On
Stall
Activates before full voltage, if the
6
current is greater than twice the
E63
nominal motor current.
(LED Stall)
Flashing
Overcurrent
It is only monitored when the SSW-08 is
at full voltage.
E66
When the parameters are set with the
factory default values this protection
(LED
trips when the motor current exceeds
Overcurrent)
3 times the value adjusted in the
Flashing
trimpot (Motor Current) for a time
longer than 1 second.
Incorrect phase
When the sequence of synchronism
sequence
signals interruptions does not follow
the RST sequence.
E67
(LED Phase Seq.)
Flashing
Undervoltage
Activates when the control supply
in the control
voltage is lower than 93 Vac.
supply
E70
(LED Fault)
Flashes twice
(LED Ready)
Off
44 | SSW-08
Table 6.1: Faults and possible causes (cont.)
Activation Description
Probable Causes
Incorrect setting of the "Motor Current"
trimpot (motor current set).
The set value is too low for the motor
being used.
Starting sequence greater than allowed.
Programmed thermal class too low.
Time between Off/On procedures lower
than that permitted by the motor power
refrigeration time.
Load on the motor shaft too high.
Thermal protection value saved when
the control is turned off and brought
back when turned back on.
Programmed time for the acceleration
ramp inferior to what is needed.
Value of the programmed current
limitation too low.
Motor locked, rotor blocked.
Programmed acceleration ramp time
lower than the actual acceleration time.
Motor shaft is locked
The transformer that supplies the motor
can be saturating and taking too much
time to recover from the starting current.
Short-circuit between phases.
Momentary motor overload.
Motor shaft is locked, rotor blocked.
Network phase sequence inverted at
the input.
May have been changed in another
place of the supply network.
Motor connection is incorrect.
Electronics supply lower than the
minimum value.
Electronics power supply with loose
contact.
Electronics power supply fuse blown.
Reset
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.