3.1.3.1 Mounting Inside a Panel
For Soft-Starters SSW-08 installed in panels or closed metallic boxes exhaustion/cooling is
required so the temperature does not exceed the maximum allowed. Refer to dissipated nominal
power in table 3.3.
10 | SSW-08
Figure 3.2: Free spaces for ventilation
Table 3.3: Dissipated power for ventilator panel dimensioning
Dissipated
Power
SSW-08
in the
Model
electronics
(W)
17 A
12
24 A
12
30 A
12
45 A
12
61 A
12
85 A
12
130 A
12
171 A
12
200 A
12
255 A
36
312 A
36
365 A
36
412 A
36
Air Flow
Outlet
Air Flow
Inlet
Total Average
Average Power
Power
dissipated
dissipated
10 starts/h
10 starts/h
3 x In @ 20 s
3 x In @ 20 s
(W)
6.8
18.8
9.6
21.6
12
18
24.4
36.4
34
52
68.4
80.4
80
102
125
146
165
C
(W)
24
30
46
64
92
138
161
182
201