Operating Range; Fixing The Burner To The Boiler - baltur GI MIST 1000 DSPGM Manual De Instrucciones

Ocultar thumbs Ver también para GI MIST 1000 DSPGM:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATING RANGE

E
N
G
L
I
S
H
DESCRIPTION OF S
BURNERS
The GI 1000 burner is a packaged version made up of separately
supplied units; these components must be connected at the burner
installation site in full observance of the instructions given by BAL-
TUR.
A - Combustion head with fan
B - Power board
C - Pumping unit for liquid fuels. If heavy oil is to be used
this unit also includes an electric heavy oil preheater
and, on request, an auxiliary steam preheater.
D - Gas valve unit for burners employing gaseous fuels (usually
methane).
These burners are available in a range of versions to suit the employed
fuel type. More specifically, these are:
- GAS (Methane) version GI 1000 DSPGN
- LIGHT OIL version GI 1000 DSPG
- HEAVY OIL (rated viscosity max. 50°E at 50°C) version GI 1000
DSPN-D
- GAS (Methane) / HEAVY OIL (rated viscosity max. 5°E at 50°C)
version GI-Mist 1000 DSPNM
- GAS (Methane) / LIGHT OIL version GI-Mist 1000 DSPGM
GI 1000 INDUSTRIAL
ERIES
Thermic capacity
Note that the GI-Mist 1000 DSPGM and GI-Mist 1000 DSPNM
burners have been designed for operation with methane gas or
with liquid fuel.
- The "GI 1000" burner is a modulating burner with a modulation
range of 1 - 4. Adjustment to current heat requirements is provided
by means of a servomotor that regulates the combined quantity of
combustion air and fuel according to the signals from the in-boiler
probe.
- The burner is fitted with a device that automatically varies the
cross-section of the air passage in the combustion head, doing
so proportionately to variations in load. This device gives optimum
combustion under all load conditions as a result of optimisation
of the air/fuel mix; there thus results reduced excess of air with
better quality combustion.

FIXING THE BURNER TO THE BOILER

Make a hole in the iron plate of the boiler in respect to the drill plate.
-
Fix the stud bolts, as supplied with the accessories. It is advi-
sable to electrically solder the bolts to the internal part of the
plate to avoid, in the event of the disassembly of the burner,
loosing them.
-
If the iron plate doesn't have insulation protection, it is neces-
sary to put insulation protection of at least 10 mm in dimension,
between the iron plate and the heater.
Check that combustion head penetrates tha combustion chamber
by the measure requested by boiler maker.
6 / 32
0006080764_201006
light oil

Publicidad

Tabla de contenido
loading