Discharge Pressure Transducer Configuration
NOTE: Be sure the transducer is set up before configuration. Refer to
page
17.
1.
Press the Auto Mode button.
2. Press Auto Mode Setup.
3. Set Pumping Behavior as Fill.
4. Set Control Sensor as Analog 1.
5. Make sure None is selected for Backup Float.
6. Choose Single Float for Float Configuration.
7.
For Action if Control Fails, choose what would happen if the control signal is lost.
•
Refer to
"Auto Mode Settings Screen Navigation" on page 16
8. For Sleep Mode, choose whether the pump should be allowed to sleep.
•
Refer to
"Auto Mode Settings Screen Navigation" on page 16
9. Set Monitoring Behavior as Maintain Pressure.
10. To start the system, refer to
Advanced Settings
For complete list of advanced parameters, refer to
6
1.
From the Home screen, select the Settings icon.
2. From the Settings screen, select the Advanced icon.
3. Enter the login information.
NOTE: To change the password, press the Change Password button, and refer to
Settings Password" on page
4. Select the desired parameter to edit.
5. Press the Advanced Settings 2 button to edit Sleep Check Time (s), Sleep Bump Timer, Sleep Delay (s),
Sleep Boost Value, Wake-Up Level, Sleep Boost Timer, and Over Pressure Timer.
•
On this screen, there is an Advanced Settings 1 button in the bottom left corner to go back.
6. Press the Settings button to go back to the settings screen.
7.
Hit the Home button at the bottom of the screen to return to the main screen.
"Discharge Pressure Transducer Control Startup" on page
"Advanced Settings Reference" on page
7
20.
"Transducer Application Setup" on
for details.
for details.
27.
35.
3
5
"Changing Advanced
DRIVE CONFIGURATION
Advanced Settings
2
19