OPERATION
Auto Mode
Level Transducer Control Startup
NOTE: Attempting to navigate away from the Auto Mode screen while the pump is in operation will cause a
warning screen to appear. Refer to
4
3
NOTE: Float switch(es) on/off status is indicated by the illustration on the screen, but does not accu-
rately portray installation depths.
1.
If not already complete, set up and configure the transducer and its application.
•
Refer to
"Transducer Application Setup" on page 17
on page
18.
2. Return to Auto Mode screen.
3. Press Level Setpoint and enter the desired level to maintain.
•
Press ENT to enter and close.
4. Choose the Units for display.
5. For applications with a backup float, press Set Backup Float Speed (Hz) to enter the desired speed to run the
pump in the event the backup float is triggered.
•
Refer to
"Backup Float Fault" on page
6. Press ENABLE button.
NOTE: When the current level is within bounds for a run command, the pump will start.
7.
Monitor rotation of the motor fan and shaft coupling.
8. If rotation is incorrect, press FWD/REV and confirm the selection in the pop-up dialog box.
•
The pump will slow to a stop, change direction, and restart automatically.
NOTE: Speed will be adjusted automatically to maintain the selected level.
9. Press DISABLE to turn off the pump and deactivate auto mode.
26
"Auto Mode" on page
24.
9
6
5
and
27.
8
"Level Transducer Control Configuration"