Backup Float Fault
If the Backup Float is triggered, the pump will enter Emergency Auto Float Control.
A red warning screen will be displayed. The pump will turn on and off as if in Single
Float control mode and run at the set speed.
To clear this fault, the Backup Float must be reset and power must be turned off for 10
seconds using the disconnect handle on the panel.
Discharge Pressure Transducer Control Startup
NOTE: Attempting to navigate away from the Auto Mode screen while the pump is in operation will cause a
warning screen to appear. Refer to
4
3
1.
If not already complete, set up and configure the transducer and its application.
•
Refer to
"Transducer Application Setup" on page 17
ration" on page
2. Return to Auto Mode screen.
3. Press Level Setpoint and enter the desired level to maintain.
•
Press ENT to enter and close.
4. Choose the Units for display.
5. Press ENABLE button.
NOTE: When the current level is within bounds for a run command, the pump will start.
6. Monitor rotation of the motor fan and shaft coupling.
7.
If rotation is incorrect, press FWD/REV and confirm the selection in the pop-up dialog box.
•
The pump will slow to a stop, change direction, and restart automatically.
NOTE: Speed will be adjusted automatically to maintain the selected level.
8. Press DISABLE to turn off the pump and deactivate auto mode.
"Auto Mode" on page
8
19.
24.
5
7
and
"Discharge Pressure Transducer Configu-
OPERATION
Auto Mode
27