AC Hardwire Output Connection
Connection for Models with Hardwire Terminals
Output Connection Requirement: UL458 requires that the output
terminals of all hardwire Inverter models must be connected to UL-
listed GFCI receptacles (Recommended receptacle manufacturer/model
series: Hubbell GF8300, Leviton 6598 or Eaton TWRSGF20). Others
may fail to operate properly when connected to this unit. When wiring
GFCI receptacles to output terminals, follow the instructions provided
with the GFCI receptacles.
1
Locate the 110V AC output terminal
(see Product Features) on the
front panel of your inverter.
2
Use a Phillips-head screwdriver to
remove the cover and access the
terminals.
3
Expose no more than 0.5 in.
(12 mm) of conductor from
each wire.
4
Thread the wires through the
strain relief. Loosen the screw
on each terminal. Place the exposed
wire end around the screw threads
(behind the screw head), then
re-tighten the screw to secure the
connection.
1
L=Line/Hot
N=Neutral
GN=Ground
2
3
4
19