TO SET THE HEATING AND SANITARY
WATER TEMPERATURE FROM THE
REMOTE CONTROL PANEL
The boiler temperature can be regulated at
intervals of 0. 1 °C by means of the keys
[SAN] and [RISC] only when there is a con-
nection.
84
SET SANITARY
[ + ] and [ - ]: increase/decrease
(+/- 0. 1 °C) sanitary water temperature
[SAN]: exit sanitary water temperature
setting
SETTING CENTRAL HEATING TEMP. WITH EXTERNAL PROBE
(automatic management of the boiler sliding temperature)
NOTE: In the zone systems the flow tem-
perature will follow the climatic logic (sli-
ding) for zone 1, while it will be fixed at the
value set on the remote control (PO ch)
for the other zones.
In the case of simultaneous requests the
boiler goes to the highest temperature
requested.
90
80
70
60
50
40
30
20
10
20
Temperatura Esterna [°C]
SET HEATING
[ + ] and [ - ]: increase/decrease
(+/- 0. 1 °C) heating temperature
[JP7 board jumper "LOW TEMP."]:
jumper disconnected: range from 40 to 80°C
jumper inserted: range from 30 to 45°C
[RISC]: exit heating temperature setting
[PO ch]: central heating max. temperature
[P1 ch]: increase/decrease (+/- 2°C) clima-
tic curve correction
[P2 ch]: setting the gradient of the curve
characteristic of central heating. By increa-
sing the gradient, represented by the
graphics below, the system flow temperature
is increased in correspondence with the
external temperature.
[SEt ch]: display of the flow set-point calcula-
ted by the board
[ + ] and [ - ]: increase/decrease
(+/- 0. 1 °C) heating temperature
JP7 board jumper "LOW TEMP."]:
jumper disconnected: range from 40 to 80°C
jumper inserted: range from 30 to 45°C
[RISC]: exit heating temperature setting
2,5
3
0
-10
External temperature (°C)
2
1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
-20