Descargar Imprimir esta página

Olimpia splendid Alysea E Instrucciones Para El Uso Y El Mantenimiento página 79

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 181
INDOOR UNIT INSTALLATION 
To perform installation of the indoor unit, please refer to the instructions below. 
For further information, please visit the product page on the website www.olimpiasplendid.com 
Step1: Select Installation location 
1.1 Ensure the installation complies with the installation minimum dimensions (defined below) and 
meets the minimum and maximum connecting piping length and maximum change in elevation 
as defined in the System Requirements section. 
1.2 Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room. 
1.3 Condensate can be easily and safely drained. 
1.4 All connections can be easily made to outdoor unit. 
1.5 Indoor unit is out of reach of children. 
1.6 A mounting wall strong enough to withstand four times the full weight and vibration of the unit. 
1.7 Filter can be easily accessed for cleaning. 
1.8 Leave enough free space to allow access for routine maintenance. 
1.9 Install at least 3 m away from the antenna of TV set or radio. Operation of the air 
conditioner may interfere with radio or TV reception in areas where reception is weak. An 
amplifier may be required for the affected device. 
1.10 Do not install in a laundry room or by a swimming pool due to the corrosive environment. 
Minimum Indoor Clearances 
ˇ15cm 
ˇ33cm  If 
the 
tube  sticks  out  from  the  left 
Ceiling 
ˇ20cm 
side. 
tube  sticks  out  from  the  right 
ˇ220cm 
Floor 
23
EN - 25
ˇ15cm 
ˇ53cm If the 
side. 

Publicidad