INDOOR UNIT INSTALLATION
Step9: Mount Indoor Unit
9.1 Slowly pass the refrigerant pipes, connecting wires and drainage hose wrapped bundle through
the wall hole.
92 Hook the top of indoor unit on the mounting plate.
9.3 Apply slight pressure to the left and right sides of the indoor unit, make sure the indoor unit is
hooked firmly.
9.4 Push down the bottom of indoor unit to let the snaps onto the hooks of the mounting plate, and
make sure it is hooked firmly.
Through‐wall
Refrigerant pipe
Drainage Hose
Connecting
Note:
The distance between the fresh air inlet and the wall should not exceed 350mm;
1.
During installation, the fresh air pipe assembly can be rotated at an appropriate angle according
2.
to the position of the outdoor unit, so that the connecting pipe does not block the fresh air inlet.
The fresh air pipe should be slightly inclined downward, and there should be no rising section to
3.
prevent rainwater from entering the room.
If it is necessary to bend the fresh air pipe, the minimum radius of the bend of the fresh air pipe
4.
should be greater than 60mm, otherwise it may affect the fresh air effect.
The fresh air inlet should not be placed in the air outlet of the outdoor unit, in a closed space or
5.
in a place with bad air.
Outdoor
Indoor
pipe
wiring
Wall sleeve
Wall sleeve
cover
Sealant
Through‐wall pipe
Refrigerant pipe
Drainage Hose
Connecting
wiring
32
EN - 34
cover
Indoor
Outdoor
Through‐wall
Refrigerant pipe
Drainage Hose
Connecting
Indoor
Outdoor
Mode1
pipe
Mode2
wiring
Mode3