Descargar Imprimir esta página

Midea MIH15GN18 Manual De Usuario E Instalacion página 41

Unidad mural
Ocultar thumbs Ver también para MIH15GN18:

Publicidad

Idiomas disponibles

Idiomas disponibles

② Connection method of the drainage pipe
Method to discharge water with the natural drainage outlet:
Method to discharge water with the drain pump:
Pipe fixture clamp
[ Caution ]
Requirements for slope of the drainage pipe:
① The branch pipes of the drainage pipe shall have a slope of at least 1% that follows the direction of water flow. Lifting
bolts shall be placed every 1–1.5m at a horizontal pipe and every 1.5–2.0m at a vertical pipe. Each vertical pipe shall
have at least two fixing points for branch pipes and lifting bolts.
② Adverse slopes are prohibited, and no water may accumulate in the elbow pipe. The outlet end shall not be immersed
in liquid.
500~1000
The drainage pipe should have a slope of 1/100 or more.
Water pump suction
500~1000
36
Installation
(Unit: mm)
Air discharge
The pipe faces
downward to avoid intake
of foreign matters.
Vertical condensate pipe
Air
The pipe
discharge
faces
downward to
avoid intake
of foreign
matters.
Ceiling
Vertical
condensate pipe

Publicidad

loading

Este manual también es adecuado para:

Mih22gn18Mih28gn18Mih36gn18Mih45gn18Mih56gn18Mih80gn18