System: The maximum total length of the P/Q communication cable of the IDU and ODU can be up to 1200m, and can
be connected in serial, as shown in the figure below:
Power supply for IDU
× ×
Circuit breaker
Master ODU
IDU 1#
CN6
CN22
P
Q
P
Q
L1
L1+La+Ln ≤ 1200m
D
P/Q/E communication
If some of the IDUs in the same refrigerant system are non-V8 series, it is required to connect "P", "Q", and "E" for
P/Q/E communication.
Single unit: Use a shielded cable for the P/Q/E communication and properly ground the shield layer. P, Q, and E
ports are located at terminal block "CN6" of the main control board. There is no distinction between
negative and positive electrodes. Connect the shield layer to the sheet metal of the electric control box,
as shown in the following figure:
System: The maximum total length of the P/Q/E communication cable of the IDU and ODU can be up to 1200m, and
can be connected in serial, as shown in the figure below:
Power supply for IDU
× ×
Circuit breaker
Master ODU
IDU 1#
CN6
CN22
P Q
E
P Q
E
L1
L1+La+Ln ≤ 1200m
Distribution box
CN1
···
2-(n-2)# IDU
N
L
La
Use shielded cables and
ground the shield layer.
Distribution box
CN1
···
2-(n-2)# IDU
L
N
La
Use shielded cables and
ground the shield layer.
Distribution box
IDU (n-1)#
CN1
CN6
L
P
Q
N
Main control board
P Q
E
CN6
Electric control box sheet metal part
Connect to the ODU PQE
IDU (n-1)#
CN1
CN6
P Q
E
L
N
51
Installation
IDU n#
CN6
R
P
Q
Ln
Distribution box
IDU n#
CN6
R
P Q
E
Ln
Communication wire
Power cable
Build-out
resistor
CN1
L
N
Communication wire
Power cable
Build-out
resistor
CN1
L
N