3. IDU and ODU communication
A
HyperLink communication (with independent power supply)
Single unit: HyperLink communication is a new type of IDU and ODU communication technology. When the IDUs
are provided with independent power supplies, use 2×1.5mm
are located at terminal block "CN10" of the main control board. There is no distinction between negative
and positive electrodes. For details, see the following figure:
[ Caution ]
Do not connect the HyperLink communication line to the PQ or D1D2 communication line.
System: The HyperLink communication line with an independent power supply between IDU and ODU can reach a
length of up to 600 meters, supporting any topology connection. The following figure shows a serial
connection:
Master ODU
CN23
M1
M2
L1
Power supply for IDU
× ×
Circuit breaker
CN1
M1
M2
CN10
L
N
IDU 1#
TO DOWN IDU
M1
M2
CN2
CN3
M1
M2
TO UP IDU
HyperLink repeater 2
L21
Power supply for IDU
× ×
Circuit breaker
CN1
M1
M2
CN10
L
N
IDU 21#
L1+La+Lx ≤ 200m
L11+Lb+Ly ≤ 200m
For other connection methods (tree topology, star topology, ring topology), please refer to the technical manual or
consult technical personnel.
Main
control
board
Connect to ODU M1M2
La
···
IDU 2-9#
Ly
Power supply for IDU
× ×
CN1
M1
M2
CN10
L
N
IDU 20#
Lc
···
IDU 22-28#
L21+Lc+L30 ≤ 200m
communication cables. M1 and M2 ports
2
CN10
M1 M2
(HyperLink)
Power supply for IDU
× ×
Circuit breaker
CN1
M1
M2
CN10
L
N
IDU 10#
Lb
Circuit breaker
···
IDU 12-19#
L30
Power supply for IDU
× ×
Circuit breaker
CN1
M1
M2
CN10
L
N
IDU 29#
48
Installation
Communication wire
Power cable
Lx
TO DOWN IDU
M1
M2
CN2
CN3
M2
M1
TO UP IDU
HyperLink repeater 1
L11
Power supply for IDU
CN1
M1
M2
L
N
CN10
IDU 11#
Power supply for IDU
CN1
M1
M2
L
N
CN10
IDU 30#
Circuit
× ×
breaker
Circuit
× ×
breaker