Descargar Imprimir esta página

Calpeda NCE HQ2 Instrucciones De Uso página 161

Bombas circuladoras de bajo consumo energético

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 98
18.5 Register list
18.5.1 Input register list – read-only (24 in total, do not use if not listed)
Address
Register name
I0
Control_version
I1
Now_speed_
I2
Igbt_vth
I3
Input_frequence
Input_voltage
I4
I5
Flt_input_power
I6
Motor_temp
I7
Run_status
I8
Device_status
I9
Fault_flag
Definition
Ranges
MCE version
1200~
Real-time speed
4200
Igbt temperature
Input frequency
Input voltage
Input power
Imotor
temperature
Start up status
0~4
Equipment
running status
Failure sign
160
Register actual
address
Remark
(hexadeci mal)
0x0600
16 bits, unsigned
0x0601
Unit: rpm
0x0602
0x0603
1 represents 0.1hz
1 represents 0.1hz
0x0603
1 represents 0.1hz
0x0603
Unit: Celsius
0x0606
"0": stop
"1": run
"2": constant speed
0x0607
(minimum)
"3":constant speed
(maximum)
"4": failure
Low bit: whether to
enter the power
limit mode (1~yes;
0x0608
0~no) High bit:
whether to enter
night mode (1~yes;
0~no)
F0: EEPROM
Failure
F1: Bus overvoltage
fault
F2: Bus undervoltage
fault
F3: overcurrent
F4: IGBT overheating
F5: Stall
F6: phase loss
F7: Motor out of control
fault - flux linkage out of
control
F9: input frequency
0x060B
failure
F10: input AC
overvoltage
F11: input AC
undervoltage
F12: communication
failure
F13: PFC bus
overvoltage fault
F14: PFC bus
undervoltage fault
F15: idle
GB

Publicidad

loading