FIRE-FIGHTING SET TO STANDARD EN 12845 – UNI 10779
HYDRAULIC DIAGRAM OF FEED BELOW HEAD
EN 12845 recommends installation below water level, with at least 2/3 of the level of water in the tank above the pumps' suction
port. Each pump has its own suction pipe at least 65 mm long.
6
2
2
2
* Components and materials NOT included in the supply of the fire-fighting pumps set
P1
Supply pump no. 1
P2
Supply pump no. 2
P3
Pilot Pump
1*
Suction interception valve
2*
Suction filter
3
Pump air and recirculating
4*
Test valve / non return valve
5
Non return valve
6*
Water reserve
7
Non return valve
8
Interception valve on delivery
9*
Pipe for pump air and recirculating
10
Diaphragm expansion tank
11
Pilot pump pressure switch
ENGLISH
DELIVERY MANIFOLD
16
17
17
13
14
9
10
7
8
5
4
3
2
2
1
1
39
21
20
19
FLOW METER STUB PIPE
16
18
12
13
15
13
14
11
12
7
4
3
2
1
12
Pressure gauge
13
Pressure switch interception valve
14
Manual test circuit non return valve
15
Main pump manual test valve
16
Interception valve on delivery
17
Pressure switch for starting electropump no. 1
18
Pressure switch for starting electropump no. 2
19*
Flow meter stub pipe
20*
Flow meter interception valve
21*
Flow meter
18
12
13
15