AVENTICS | DeviceNet | R402003659–BAL–001–AG
Appendix – Bus master configuration
Parameter Data Length
Parameter Data,
Device Parameter Data
Determines the parameter data length. With the bus control, the
length is: 0x01 Byte.
Both these have the same functions and are identical.
W
With these a parameter setting can be written into the module and
the diagnostics can be activated and deactivated.
W
In the opposite direction, the parameter settings can be read out.
The default value of these parameters (after power-on) depends on the
position of the S3.5 switch (see "Setting diagnostic messages" on page
69):
S3.5 = OFF default value: 0x00
S3.5 = ON default value: 0x3F
In order to activate the switch over of diagnostics from ON to OFF
(or vice versa) during operation, the module must be stopped and
then started again. (power-on). The transmitted data length
changes. This therefore has to be adapted also in the control
system.