Base Binary Inputs; Base Analogue Outputs - Ecolab Versatronic Instrucciones De Servicio

Ocultar thumbs Ver también para Versatronic:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7.5.3

Base binary inputs

Plug /
terminal Connection option
IN 1 to 3
Binary input (floating contact) a
In the configuration of the binary input, set "Contact" to "Potential free contact".
Binary (external power
source)
In the configuration of the binary input of the "Contact" must be set to "external
power source".
Binary input (NPN transistor
switching output)
In the configuration of the binary input, set "Contact" to "Potential free contact".
Binary input (PNP transistor
switching output)
In the configuration of the binary input of the "Contact" must be set to "external
power source".
(
1
) For the power supply of sensors with 24 V DC of the power supply output PWR is 24V available.
7.5.4

Base analogue outputs

Plug / terminal
OUT 4
OUT 5
Wire Potential
b
a
b
1
a (
)
b (
1
)
c
d
1
a (
)
b (
1
)
c
d
Connection option
analogue output DC 0 to 10 V DC or 0 (4) to 20 mA
(configurable)
analogue output DC 0 to 10 V DC or 0 (4) to 20 mA
(configurable)
57
Electrical connection
Terminal
PWR
IN 1
24V
Floating
28
contact
29
Logical signal
28
+
Logic signal -
29
Sensor +
42
sensor -
43
Switching
28
signal
(collector)
sensor -
29
Sensor +
42
sensor -
43
Switching
28
signal
(collector)
sensor -
29
Symbol
IN 2
IN 3
30
32
31
33
30
32
31
33
30
32
31
33
30
32
31
33
Symbol
417102269 Rev. 2-08.2020