Device menu
10.4.7

Threshold monitoring

Call Limit monitoring: Device menu è Configuration è Limit monitoring è Limit
monitoring functions 1 to 8
Configuration
point
Name
Input signal
Alarm
Binary signal for
Hold
Hold behaviour
Behaviour with
calib.
Error Handling
Alarm 1
Alarm type
Alarm / event list
Alarm text
Threshold
Hysteresis
Alarm delay on
Alarm delay off
alarm 2
Alarm type
Alarm / event list
Alarm text
Threshold
417102269 Rev. 2-08.2020
Selection /
option
Explanation
Up to 15
Input name
characters of text
Select from
Signal source of the analogue value, which is
analogue sector
monitored by threshold monitoring
Select from
Select the binary signal source to enable the limit
analogue sector
switches in Hold mode
Inactive
Behaviour of the limit switch in Hold mode
Active
Frozen
Inactive
Behaviour of the limit switch during calibration
Active
Frozen
Normal
Inactive
Behaviour of the limit switch upon occurrence of
Active
a fault alarm
Frozen
Inactive
Choice of alarm type
Min. alarm
Max.- alarm
alarm window
Alarm window
invert.
OFF
OFF: Alarm is not displayed
Alarm
Alarm: Alarm is displayed in the alarm bar of the
Event
display
Event: Al. is only displayed in the event list
Up to 20
Text which is displayed when an alarm is in the
characters of text
display and/or is on the event list.
-99999 to +99999 Threshold at which an alarm is triggered
(depending on the type of alarm)
0 to 99999
Distance to the threshold
Alarm on =
< Thresh. – Hyst. (With minimum alarm)
> Thresh. + Hyst. (With max. alarm)
Alarm OFF =
> Threshold (with minimum alarm)
< Threshold (with max. alarm)
0 to 999 s
Time delay between occurrence of the alarm
condition and the alarm turning on
0 to 999 s
Time delay between end of the alarm set to on
and the alarm turning off
Inactive
Choice of alarm type
Min. alarm
Max.- alarm
alarm window
Alarm window
invert.
OFF
OFF: Alarm is not displayed
Alarm
Alarm: Alarm is displayed in the alarm bar of the
Event
display
Event: Al. is only displayed in the event list
Up to 20
Text which is displayed when an alarm is in the
characters of text
display and/or is on the event list.
-99999 to +99999 Threshold at which an alarm is triggered
(depending on the type of alarm)
166
Default
X threshold
No selection
No selection
Inactive
Normal
Inactive
Inactive
Alarm
Alarm 1
Temp.input 1
0,00
0,00
0 sec
0 sec
Inactive
Alarm
Alarm 2
Temp.input 1
0,00