4. Access to measurements and personalisation data
UPS set-up

Local settings

Function
Language
Date / Time Format
Date / Time Change
Audible Alarm

Output settings

Function
Output Voltage
Freq Converter
Output Frequency
Bypass Transfer
Interrupt Time
Overload Prealarm
Redundancy Mode
Redundancy Level

ON/OFF settings

Function
Cold Start
Forced Reboot
Auto Restart
Energy Saving
Sleep Mode
Remote Command
-
34008486EN/AC
Page 32
Factory setting
Options
English
French, German, Italian, Portuguese, Spanish
International
US (MM-DD-YYYY/HH:MM AM/PM)
(DD-MM-YYYY/HH :MM)
GMT + 1
MM-DD-YYYY/HH :MM adjustable
(Continental Europe)
Yes
No
Factory setting
Options
230 V
200 V / 208 V / 220 V /
240 V / 250 V
Disable
Enable
50 Hz
60 Hz
Yes
No
10 ms
20 ms, ...... , 200 ms
105 %
40 %, 50 %, 70 %
No
Yes
1
2,3
Factory setting
Options
Disable
Enable
Enable
Disable
Enable
Disable
Disable
Enable
Enable
Disable
Enable
Disable
Comments
User selectable under frequency-
converter mode
Transfer to bypass if Normal AC
source is out of tolerance
Break time calibration during load
transfer on Normal AC source out
of tolerance
Alarm if threshold is overrun
Alarm if redundancy loss
On redundancy Mode:number of
redundant modules needed
Comments
Start on battery
Enables automatic restart of the
system even if Normal AC source is
restored before the end of the
shutdown sequence
UPS restarts automatically when
Normal AC source is restored
Automatic shutdown on battery if
output load level < 10 %
Enables consideration of shutdown
or restart orders from software to
be authorised