Ups Set-Up; Local Settings; Output Settings; On/Off Settings - Eaton Pulsar Serie Manual De Instalación Y De Usuario

Ocultar thumbs Ver también para Pulsar Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.4

UPS Set-Up

Local Settings

Function
Language
Date/Time Format
Date/Time Change
Audible Alarm

Output Settings

Function
Output Voltage
Freq Converter
Output Frequency
Eco Mode
Slew rate
Bypass Transfer
Interrupt Time
Overload Prealarm

ON/OFF Settings

Function
Cold Start
Forced Reboot
Auto Restart
Energy Saving
Sleep Mode
Remote Command
86-87021-00 A01 - Page 30
Factory Setting
English
International format
(DD-MM-YYYY/HH :MM)
GMT+ 1(Continental Europe)
Yes
Factory Setting
208V
Disabled
60 Hz
Disabled
1 Hz/sec.
Yes
10 ms
105%
Factory Setting
Disabled
Enabled
Enabled
Disabled
Enabled
Enabled
Options
French, German, Italian, Portuguese, Spanish
US (MM-DD-YYYY/HH:MM AM/PM)
MM-DD-YYYY/HH :MM adjustable
No
Options
200V / 230V / 220V /240V / 250V
Enabled
50 Hz
Enabled
0.5 Hz/sec.
No
20 ms, ...... , 200 ms
40%, 50%, 70%
Options
Enabled
Enabled
Disabled
Enabled
Disabled
Disabled
Comments
Bypass is disabled
User selectable under frequen-
cy-converter mode
Transfer to bypass if Normal AC
source is out of tolerance
Break time calibration during
load transfer on Normal AC
source out of tolerance
Alarm if threshold is overrun
Comments
Start on battery
Enables automatic restart of
the system even if Normal AC
source is restored before the
end of the shutdown sequence
UPS restarts automatically
when Normal AC source is
restored
Automatic shutdown on battery
if output load level < 10%
Enables consideration of
shutdown or restart orders from
software to be authorized

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido