Electrical Connections
NOTE: Run wires 23, 194 and 0 through the wire shielding provided in the manual bag to separate the low volt-
age from the high voltage wires unless the requirement of 300.3(c)(1) of the NEC are met (see the Parts
Shipped Loose section).
NOTE: Regardless of whether unit is running or not, T1 must be connected to keep battery charged.
6.3 — Main AC Wiring
28
Figure 6-1. Control Wiring (Behind Control Board)
Figure 6-2. Main AC Wiring
4-6 AWG 3.95 Nm
(35 in-lbs)
8 AWG 2.82 Nm
(25 in-lbs)
10-14 AWG 2.26 Nm
(20 in-lbs)
Large Ground
Torque Spec 2/0 to
14 AWG 13.56 Nm
(120 in-lbs)
Installation Guidelines for Air-Cooled Generators