salmson Control EC-L Instalacion Y Puesta En Servicio página 56

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

English
Menu 5.00: Installation (basic settings of the switchgear)
No.
Description
Automatic resetting of error
"Dry run"
5.65
Values: off, on
Factory setting: off
Integrated buzzer On/Off
5.66
Values: off, on
Factory setting: off
Output for an external signalling
unit On/Off
5.67
Values: off, on
Factory setting: off
Rotating fi eld monitoring
(mains connection) On/Off
5.68
Values: off, on
Factory setting: on
Internal motor current
measurement On/Off
5.69
Values: off, on
Factory setting: on
Menu 6.00: Fault memory
No.
Alarm acknowledgement
6.01
--> "On" acknowledges alarms
10x fault memory locations
Error code is displayed
6.02...11
(FiFo principle: latest error
below 6.02)
Menu 7.00: Service
No.
Description
Enable change in parameters
7.01
Values: off, on
Factory setting: off
Input of serial number
(fi rst 4 digits)
7.04
Value range: 0000...9999
Factory setting: Device ID
Input of serial number
(next 4 digits)
7.05
Value range: 0000...9999
Factory setting: Device ID
Activate EasyActions
7.06
Values: off, on
Factory setting: on
Activate the service interval
indicator
7.07
Values: 0; 0.25; 0.5; 1; 2 years
Factory setting: 0
Reset the service interval
7.08
indicator
--> "on" resets the interval
* The value range is dependent on the sensor
measuring range and other parameters!
** See the function description below
56
Display
Description
Display
Display
OPERATION AND FUNCTION
7.5.2. Explanation of individual functions and settings
Menu 5.03 / Standby pump
It is possible to use one pump as a standby pump.
This pump is not activated in normal operation. It
is only activated if a pump malfunctions due to a
fault.
The standby pump is subject to standstill
monitoring however and is activated during
pump cycling and pump kick.
Menu 5.07 / Sensor type for level control
The switchgear can be operated for measuring
the level with the following signal transmitters:
• "Float": Float switch
• "Level": Level sensor
• "Bell": Dynamic pressure bell
• "Opt01": Enables the connection of a level
monitor with the following switching points:
• Pump 1 ON/OFF
• Pump 2 ON/OFF
• High water level
The principle sequence for activating and deac-
tivating individual pumps is similar to operation
with discrete fl oat switches. The internal con-
struction of the level monitor assures hysteresis
between the activation/deactivation level of the
relevant pump.
Additionally, a fl oat switch for dry-running pro-
tection can be installed for increased operational
reliability.
Menu 5.39 / Alarm signal when switching off
the pumps via "External OFF"
The pumps can be switched on and off via a sep-
arate signal transmitter (e.g. fl oat switch) via the
"External OFF" contact. This enables additional
dry-running protection to be realised for example.
This function overrides all other switching points
and all pumps are switched off. If this function
is used, you can stipulate how alarm signalling
should take place in case of an open contact here:
• "off": Pump(s) are switched off, there is only an
optical signal as a symbol on the LCD
• "on": Pump(s) are switched off, there is an optical
signal as a symbol on the LCD and an additional
alarm signal.
Menu 5.40 / Pump kick
To prevent longer standstill times for the
connected pumps, a periodical test run can be
performed (pump kick function).
If pump kick is activated, the following parame-
ters must be set:
• Menu 5.41: Defi nition whether pump kick should
also take place if pumps are switched off via
"External Off".
• Menu 5.42: Time interval after which a pump kick
should take place.
• Menu 5.43: Running time of the pump kicks.
Wilo Salmson France SAS 03-2017 V05 DIN A4

Publicidad

Tabla de contenido
loading

Tabla de contenido