Menu Control And Structure - salmson Control EC-L Instalacion Y Puesta En Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

English
Level measurement with level sensor or
dynamic pressure bell
Fig. 7: Illustration of the switching points with a level sensor in the
"Drain" operating mode using the example of 2 pumps
1 Pump 1 ON
2 Pump 1 OFF
3 Pump 2 ON
4 Pump 2 OFF
* Also realised via a separate fl oat switch for increased
operational reliability.
A level sensor or a dynamic pressure bell can be
connected to the switchgear, whereby up to
8 switching points can be defi ned for controlling
a maximum of 3 pumps:
• Pump 1 On/Off
• Pump 2 On/Off
• Pump 3 On/Off
• Dry-running level
• High water level
7.2.2. "Fill" operating mode
The reservoir is fi lled up, for instance, to pump
water out of a well into a rainwater storage tank.
The connected pumps are activated when the
level falls and switched off when the level rises.
This control is mainly used for water supply.
Level measurement with fl oat switch
Fig. 8: Illustration of the switching points with a fl oat switch in the
"Fill" operating mode using the example of a submersible pump
1 Pump ON
2 Pump OFF
5 Dry-running level in the well
Up to 5 fl oat switches can be connected to
the switchgear for controlling a maximum of
2 pumps:
• Pump 1 ON
• Pump 2 ON
• Pump 1 and 2 OFF
• Low water level in the tank to be fi lled
• High water level
• Dry-running level in the well (realised via a
separate fl oat switch at the input "Ext. OFF")
The fl oat switch should be equipped with a nor-
mally closed contact, i.e. on reaching or exceeding
the switching point, the contact is opened.
52
5 Dry-running level
6 High water level
7 Dry-running level*
8 High water level*
3 High water level
4 Low water level
Level measurement with level sensor or
dynamic pressure bell
Fig. 9: Illustration of the switching points with a level sensor in the
"Fill" operating mode using the example of a submersible pump
1 Pump ON
2 Pump OFF
5 Dry-running level in the well
A level sensor or a dynamic pressure bell can be
connected to the switchgear, whereby up to
8 switching points can be defi ned for controlling
a maximum of 3 pumps:
• Pump 1 On/Off
• Pump 2 On/Off
• Pump 3 On/Off
• Low water level in the tank to be fi lled
• High water level
• Dry-running level in the well (realised via a
separate fl oat switch at the input "Ext. OFF")

7.3. Menu control and structure

7.3.1. Control
Fig. 10: Operation
The menu is controlled via the operating button:
• Turn: Selection and set values
• Press: Change menu level or confi rm value
7.3.2. Structure
The menu is divided into two areas:
• EasyActions menu
• Parameter menu
Call EasyActions menu
The EasyActions menu offers quick access to the
following functions:
• Resetting error messages (only displayed if
error messages exist)
• Manual operation of pump 1
• Manual operation of pump 2
• Manual operation of pump 3
1. Turn the operating button by 180° to call the fi rst
function.
2. Continue to turn the operating button by 180° at
a time to call additional functions or to go back to
the main screen.
NOTE
This EasyActions menu can be disabled in the
menu 7.06!
Wilo Salmson France SAS 03-2017 V05 DIN A4
OPERATION AND FUNCTION
3 High water level
4 Low water level

Publicidad

Tabla de contenido
loading

Tabla de contenido