16. RESET:

The error condition can be reset through the reset button at the front of the SSW-05 Plus, or through a momentary
contact closure (0.5 seconds) at DI2 (digital input for reset). Other alternative to reset the SSW-05 Plus is by
switching On/Off the power control supply of the electronics (A1 and A2).
Note:
The SSW-05 Plus also provides the automatic reset by enabling this function through the dip-switch (auto):
1) The automatic reset occurs after 15 minutes in the following fault conditions:
- Overcurrent, Phase Loss, Locked Rotor, Immediate overcurrent of the SSW-05 Plus by-pass relay, Overcurrent
before By-pass, Frequency out of tolerance, Contact of the internal By-pass relay is open and power control
supply undervoltage.
2) For incorrect phase sequence there is no automatic reset.
3) For motor overload and thyristor overload there is a specific algorithm for the automatic reset time.
VERY IMPORTANT!
Both digital input (DI2) and reset button of the SSW-05 Plus should be used only for the reset after a fault condition.
If the reset function is used when the SSW-05 Plus is operating at rated voltage, the internal by-pass relays will open
their contacts under load, thus jeopardizing their life.
17. FAULTS AND POSSIBLE CAUSES:
When a fault is detected, the Soft-Starter is disabled and the Fault Code is displayed by flashing LED´s or on the
readout display in the EXX form, where XX is the actual Fault Code.
To restart the Soft-Starter after a fault has occurred, the Soft-Starter must be reset. In general, the reset can be made
as follows:
disconnecting and reapplying the AC power (power-on reset);
by pressing the key "RESET" on the SSW05-RS front panel (reset key);
through the HMI-SSW05-RS by pressing the key
automatic reset by enabling the function through the dip-switch (auto) or though P106 and P220.
via digital input: DI2.
Table below explains how to reset the fault and show the possible causes for each Fault Code.
Protection
Description
Phase Loss
(Phase Loss)
Motor Overload
Available only when
External Fault
HMI-SSW05-RS or serial
communication is used
(see chapter 19)
Available only when
Error in the Copy
HMI-SSW05-RS is used
Function
(see chapter 19)
Fault Display
SSW-05
HMI-SSW05-RS
Front Panel
(see chapter 19.3)
LED
E03
LED
E05
(Overload)
E06
E10
English-13
(manual reset);
Reset
Power-on
Phase fault in the three-phase
Reset key
network
key
Short-circuit or thyristor fault
Auto-reset
Motor is not connected
DI2.
Motor connection is not correct
Power-on
"Motor Current" trimpot or P105
key
(motor current) has been set
Auto-reset
incorrectly. The set value is too
low for the motor being used.
Load on the motor shaft too high.
Too much successive motor starts.
Power-on
The wiring at DI1 is open (not
Reset key
connected).
key
DI2.
Power-on
Keypad cable misconnected.
key
Electrical noise in the
installation (electromagnetic
interference).
Possibles Causes