20. TABLE OF PARAMETERS (FOR SERIAL COMMUNICATION / HMI-SSW05-RS):
Parameter Function
Parameter
(Reading)
(2)
P000
Parameter Access
P002
Motor Current Indication (%)
P003
Motor Current Indication (A)
P023
Software Version
Status Indication of the
P050
motor overload protection
Parameter Function
Parameter
(Reading and Writing)
P101
Initial voltage
P102
Time of the Acceleration Ramp
P104
Time of the Deceleration Ramp 0 ... 20 (s)
(1)
P105
Motor Current Setting
(1)
P106
Protection Configuration
P204
(1)
Load Factory Setting
(1)
P215
Keypad Copy Function
HMI/(Trimpots and Dip Switch)
P220
(1)
Selection
Programmable Digital Input
(1)
P264
DI 1
Programmable relay output
(1)
P277
(14/23 - 24)
P295
(1) (2)
Rated current of the Soft-Starter
P308
Network Address
Action of the serial
P313
communication verification
Verification Time of the
P314
Serial Communication
(1)
These Parameters can be changed only with stopped motor.
(2)
These Parameters are not changed through the function "Loads Parameters with Factory Setting" (P204).
Range of the
Internal Values
0 ... 4, 6... 9999 = Read
5 = Alteration
000,0 ... 999,9 (% In)
000,0 ... 999,9 (A)
0 ... 250
250 = error
Range of the
Internal Values
30 ... 80 (% Un)
1 ... 20 (s)
30 ... 100 (%)
0 ... 3F Hexadecimal
0 = No function
1 = No function
2 = No function
3 = No function
4 = No function
5 = Load factory default
0 = Off
1 = Copy (SSW -> keypad)
2 = Paste (keypad -> SSW)
0 = Trimpots and Dip Switch
1 = HMI
0 = Not used
1 = Enable / Disable
2 = External Fault
1 = Full voltage
2 = Error
3 = Serial Com.
0 = 3 A
1 = 10 A
2 = 16 A
3 = 23 A
4 = 30 A
5 = 45 A
6 = 60 A
7 = 85 A
1 ... 30
1 = only Error
2 = ramp disabling
3 = General disabling
4 = P264 → 1
0 ... 5 (s)
English-20
Factory
User
Page
Setting
Setting
0
21
21
21
21
21
Factory
User
Page
Setting
Setting
30
21
10
22
0 = off
22
100
22
1F Hex.
22
0
25
0
25
0
26
1
26
1
26
According
26
to the Type
1
26
26
0 = oFF
27