11.3. Start/Stop by using Push Button and Operation Function Relay of the SSW-05 Plus:

12. SSW-05 PLUS SETTING:

12.1. Pedestal Voltage Setting:

Set the pedestal voltage to a value that the motor starts to run as soon as run command is given by the SSW-05
Plus.
Trimpot for the
voltage setting

12.2. Setting of the acceleration ramp time:

Set the value so that the motor accelerates to the rated speed.
Note: Please consider that in the cases where rated SSW-05 Plus current is equal to the rated motor current,
the SSW-05 Plus can be operated, at maximum, during 10 seconds at 3 x I
Trimpot for
acceleration
Ramp time
pedestal
the
setting
English-8
Symbol
Description
Fuse
Disconnecting Switch
(opens under load)
Transformer
N.O. switch
(with holding)
N.C. push button
(with automatic return)
N.O. push button
(with automatic return)
Contactor (coil)
Three-phase induction
motor
The "T1" transformer is only required when the
line voltage is out of the range allowed for the
electronics supply (90 – 250Vac). For 400V,
use neutral conductor (N) and one phase.
The dot
indicates the
factory default
.
N