Power On
Before turning on the power supply,
Make sure all wires are connected properly.
Make sure no screws, loose wire ends or tools are left in the drive.
After turning the power on, the drive mode display should appear and no fault or
alarm should be displayed.
Control Mode Selection (A1-02)
There are three control modes available. Select the control mode that best suits the
application the drive will control.
Control Mode
V/f Control
Open Loop
Vector Control (OLV)
PM Open Loop
Vector Control
Normal / Heavy Duty Selection (C6-01)
The drive supports two ratings, Normal Duty and Heavy Duty. Both have different output
current ratings (refer to the catalog or Technical Manual). Set the Duty mode in accor-
dance with the application.
Mode
C6-01
Application
Overload capability (OL2)
L3-02 Stall Prevention
during Acceleration
L3-06 Stall Prevention
during Run
Default carrier frequency
Parameter
• General variable speed applications, particularly useful for
A1-02 = 0
running multiple motors from a single drive
(default)
• When replacing a drive in which parameter settings are
unknown
• General variable speed applications
A1-02 = 2
• Applications requiring high precision, high speed control
• Derated torque-load applications employing permanent mag-
A1-02 = 5
net motors (SPM, IPM) and energy savings.
Heavy Duty Rating (HD)
0
Applications with a constant torque
like extruders, conveyors and
cranes. High overload capability
might be needed.
150% of drive rated current for 60
s
150%
150%
8 kHz
Main Applications
Normal Duty Rating (ND)
Applications where the torque increases with the
speed like fans or pumps. High overload tolerance
is normally not needed.
120% of drive rated current for 60 s
19
5 Start Up
1
120%
120%
Swing PWM