6 Electrical Connection
Position
Designation
C
Router K201, Pin
connector X3
Router K201, Pin
connector X4
Router K201, Pin
connector X5/X6
Router K201, Pin
connector X7/X8/
X9
Router K201, Pin
connector X10
D
Connecting terminal
plate X300
E
Connecting terminal
plate X200
F
Connecting terminal
plate X700
G
Connecting terminal
plate X701
H
Connecting terminal
plate X702
I
Connecting terminal
plate X703
K
Connecting terminal
plate X100
* If the Fuel Save Controller has been ordered with the optical-fiber module, the optical-fiber module is plugged in upon delivery.
6.1.3

Assignment of the jumpers

The jumpers supplied or premounted in the Fuel Save Controller are assigned to the connecting terminal plates
mentioned in the following table.
Color of the
Assignment of
jumper
the jumper
Blue
Connecting ter-
minal plate
X200
20
FSC20-IA-xx-20
Description
Connection for external communication network(see Section 6.9, page 42)
Reserved for internal wiring of the Fuel Save Controller
Connection for communication with inverters(see Section 6.8.2, page 35)
Terminal for genset control or utility grid synchronization control (see Sec-
tion 6.8.4, page 37)
Reserved for extensions of the photovoltaic diesel hybrid system, e.g. for the com-
munication connection of a Data Acquisition Module or the connection of a
SMA Cluster Controller / SMA Inverter Manager for the evaluation of tempera-
ture or irradiation sensors.
Terminal for supply voltage (see Section 6.3, page 21)
Terminal for voltage measurement:
In the basic configuration, only the terminals X200:1 to X200:6 are available for
voltage measurement (see Section 6.7.3, page 32).
Terminal for the current transformer
In the basic configuration, only the terminals X700:1 to X700:13 are available
for current measurement (see Section 6.7.2, page 29).
Terminal for analog inputs:
In the basic configuration, no analog inputs are available (see Section 6.6,
page 25).
Switching inputs for the connection of switches (see Section 6.4, page 22)
Switching outputs for the connection of contactors (see Section 6.5, page 24)
For grounding the Fuel Save Controller (see Section 6.2, page 21)
Information on the use of the jumper
(see Section 6.7.3 "Connecting the Voltage Measurement", page 32)
SMA Solar Technology AG