Connecting The Communication With The Genset Control System Via Can Network - SMA FUEL SAVE CONTROLLER 2.0 Instrucciones De Instalación

Ocultar thumbs Ver también para FUEL SAVE CONTROLLER 2.0:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SMA Solar Technology AG
☐ Type of plug: RJ45
☐ RJ45 plugs used for installation cables must have a metal enclosure. The cable shield must be connected on both
ends of the installation cable.
Procedure:
1. Insert the cable into the Fuel Save Controller (see Section 9.1, page 47).
2. Connect the cable to the router K201 at the pin connector X3.
3. Activate the DHCP protocol on the router of the external communication network.
6.10
Connecting the Communication with the Genset Control System via
CAN Network
You can connect the Fuel Save Controller to a CAN network using a D-sub connector. The Fuel Save Controller can
communicate with the genset control units via the CAN network.
D-sub plug assignment:
Figure 19: D-sub plug assignment
Position
Pin
A
B
C
D
E
F
G
H
I
Interference of network data transmission due to AC cables
When AC cables are in operation, they generate an electromagnetic field which may induce leading or lagging
interference in network cables during data transmission.
• Lay the network cables using suitable fastening material while observing a minimum clearance of 50 mm to
the AC cables.
Installation Manual
Signal
1
2
CAN_L
3
CANGND
4
5
6
GND
7
CAN_H
8
9
6 Electrical Connection
FSC20-IA-xx-20
43