11 Technical Data

Mechanical Data

Width x height x depth
Maximum weight
Degree of protection according to IEC 60529

Ambient Conditions

Operating temperature
Humidity, non-condensing
Maximum operating altitude above MSL

Voltage supply

Operating voltage range
Maximum input voltage
Overvoltage category
Frequency
Maximum power
Maximum back-up fuse
Type of connection
Conductor cross-section
* in accordance with IEC 60664-1
Reverse power limits for gensets
Maximum permitted reverse power of a genset relative to
its nominal power
Standby time until required grid disconnection at a re-
verse power of 30%*
Standby time until required grid disconnection at a re-
verse power of 10% to 30%*
Standby time until required grid disconnection at a re-
verse power of 5% to 10%*
Grid disconnection at a reverse power of less than 5%*
* In relation to the nominal power of the gensets
System limits for PV inverters*
Maximum permitted number of PV inverters
Maximum permitted nominal power of all PV inverters
* in the basic configuration
Installation Manual
11 Technical Data
760 mm x 760 mm x 210 mm
48 kg
IP65
-10°C to +50°C
5% to 95%
2000 m
110 V to 240 V
260 V
III*
50 Hz to 60 Hz
200 W
Circuit-breaker 16 A, type B
Spring-cage terminal
1.5 mm² to 2.5 mm²
30 %
at least 0.3 s
at least 1 s
at least 3 s
is prohibited
64
1 MW
FSC20-IA-xx-20
51