Aventics AES Serie Descripción De Sistema página 101

Ocultar thumbs Ver también para AES Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 255
AVENTICS | Bus Coupler AES/Valve Driver AV, EtherNet/IP | R412018139–BAL–001–AF
Table 21:
14
Designation
UL
15
UA
UL (14)
16
MOD
NET
UA (15)
17
L/A 1
L/A 2
18
MOD (16)
19
NET (17)
L/A 1 (18)
L/A 2 (19)
1)
At least one of the two LEDs L/A L/A 1 and L/A 2 must be illuminated or illuminated in green and flashing quickly in yellow.
Depending on the data exchange, the flashing may be so fast that it appears that the LED is illuminated. This color is then light
green.
If the diagnostic run is successful, you may commission the valve system. Otherwise, the errors
must be remedied (see section 13 "Troubleshooting" on page 119).
3. Switch on the compressed air supply.
Status of the LEDs on commissioning
Color
State
Green
Illuminated
Green
Illuminated
Green
Illuminated
Green
Illuminated
Yellow
Flashes quickly
Yellow
Flashes quickly
Commissioning the Valve System with EtherNet/IP
Meaning
The electronics supply voltage is greater than the lower
tolerance limit (18 V DC).
Actuator voltage exceeds the lower tolerance limit
(21.6 V DC).
The configuration is OK and the backplane is working
perfectly.
The bus coupler exchanges cyclical data with the
controller.
1)
Connection with Ethernet device on fieldbus connection
X7E1
1)
Connection with Ethernet device on fieldbus connection
X7E2
101

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aes-d-bc-eip

Tabla de contenido