Led Diagnosis On The Bus Coupler - Aventics AES Serie Descripción De Sistema

Ocultar thumbs Ver también para AES Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 255
102
AVENTICS | Bus Coupler AES/Valve Driver AV, EtherNet/IP | R412018139–BAL–001–AF

LED Diagnosis on the Bus Coupler

Reading the diagnostic display
on the bus coupler
UL
UA
MOD
NET
L/A 1
L/A 2
11 LED Diagnosis on the Bus Coupler
The bus coupler monitors the power supplies for the electronic components and actuator control.
If they exceed or fall below a set threshold, an error signal will be generated and reported to the
controller. In addition, the status is displayed by the diagnostic LEDs.
The LEDs on the top of the bus coupler reflect the messages listed in Table 22.
Before commissioning and during operation, regularly check the bus coupler functions
by reading the LEDs.
Table 22:
Meaning of the diagnostic LEDs
14
Designation
Color
15
UL (14)
Green
16
Red
17
Red
18
Green/red
19
UA (15)
Green
Red
Red
MOD (16)
Green
Green
Red
Red
NET (17)
Green
Green
Red
Red
Green/red
L/A 1 (18)
Green
Yellow
Green/
yellow
L/A 2 (19)
Green
Yellow
Green/
yellow
State
Meaning
Illuminated
The electronics supply voltage is greater than the lower
tolerance limit (18 V DC).
Flashes
The electronics supply voltage is less than the lower tolerance
limit (18 V DC) and greater than 10 V DC.
Illuminated
The electronics supply voltage is less than 10 V DC.
Off
The electronics supply voltage is significantly less than 10 V DC
(limit not defined).
Illuminated
Actuator voltage exceeds the lower tolerance limit (21.6 V DC).
Flashes
The actuator voltage is less than the lower tolerance limit
(21.6 V DC) and greater than UA-OFF.
Illuminated
The actuator voltage is less than UA-OFF.
Illuminated
The configuration is OK and the backplane is working perfectly.
Flashes
The module has not yet been configured (there is no connection
to a master).
Flashes
Diagnostic message from module present
Illuminated
Valve unit incorrectly configured or backplane function error
Illuminated
The bus coupler exchanges cyclical data with the controller.
Flashes
Waiting to establish communication with the controller
Flashes
Communication was disrupted (no communication with the
master)
Illuminated
Severe network problems, IP address assigned twice
Off
An IP address has not yet been assigned and the DHCP service is
off.
Illuminated
The physical connection between the bus coupler and network
has been detected (link established).
Flashes
Data packets received (flashes for each data packet received)
quickly
Off
The bus coupler does not have a physical connection with the
network.
Illuminated
The physical connection between the bus coupler and network
has been detected (link established).
Flashes
Data packets received (flashes for each data packet received)
quickly
Off
The bus coupler does not have a physical connection with the
network.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aes-d-bc-eip

Tabla de contenido