Presettings On The Bus Coupler; Opening And Closing The Window; Changing The Address - Aventics AES Serie Descripción De Sistema

Ocultar thumbs Ver también para AES Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 255
AVENTICS | Bus Coupler AES/Valve Driver AV, EtherNet/IP | R412018139–BAL–001–AF

9 Presettings on the Bus Coupler

Configuration error!
An incorrect valve system configuration can cause malfunctions in and damage to the overall
system.
The configuration may therefore only be carried out by qualified personnel (see section 2.4
"Personnel qualifications" on page 71).
Observe the specifications of the system owner as well as any restrictions resulting from the
overall system.
Observe the documentation of your PLC configuration program.
The following pre-settings must be made using the PLC configuration program:
Assigning a unique IP address to the bus coupler and adjusting the subnet mask (see section 9.3
"Assigning IP address and subnet mask" on page 96)
Setting the parameters for the bus coupler, i.e. writing the last byte of the output data with
the parameter (see section 5.5 "Setting the bus coupler parameters" on page 84)
Setting the module parameters via the controller (see section 5.5.1 "Setting parameters for the
modules" on page 84)
9.1

Opening and closing the window

3
25
Defective or improperly positioned seal!
Water may enter the device. The protection class IP65 is no longer guaranteed.
Make sure that the seal below the window (3) is intact and properly positioned.
Make sure that the screw (25) has been securely tightened with the correct torque (0.2 Nm).
1. Loosen the screw (25) on the window (3).
2. Lift up the window.
3. Carry out the settings as described in the next steps.
4. Close the window. Ensure that the seal is positioned correctly.
5. Tighten the screw.
Tightening torque: 0.2 Nm
9.2

Changing the address

An address change will not be effective during operation!
The bus coupler will continue to work with the previous address.
Never change the address during operation.
Disconnect the bus coupler from the power supply UL before changing the positions of
switches S1 and S2.
Presettings on the Bus Coupler
NOTICE
NOTICE
NOTICE
95

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aes-d-bc-eip

Tabla de contenido