AVENTICS | Bus Coupler AES/Valve Driver AV, EtherNet/IP | R412018139–BAL–001–AF
Conversion of the Valve System
PLC configuration key
12.5.5

Conversion documentation

After a conversion, the PLC configuration key printed on the right end plate is no longer valid.
Correct the PLC configuration key or cover it with a new label and write the new PLC
configuration key on the end plate.
Always document all changes to your configuration.
Mat. no.
After a conversion, the material number (MNR) on the right end plate is no longer valid.
Mark the material number so that it is clearly visible that the unit no longer corresponds to its
original condition on delivery.

12.6 Conversion of the I/O zone

12.6.1

Permissible configurations

No more than ten I/O modules may be connected to the bus coupler.
For further information on converting the I/O zone, see the system descriptions of the individual
I/O modules.
We recommend an expansion of the I/O modules starting from the left end of the valve system.
12.6.2
Conversion documentation
The PLC configuration key is printed on the top of the I/O modules.
Always document all changes to your configuration.

12.7 New PLC configuration for the valve system

Configuration error!
An incorrect valve system configuration can cause malfunctions in and damage to the overall
system.
The configuration may therefore only be carried out by an electrical specialist!
Observe the specifications of the system owner as well as any restrictions resulting from the
overall system.
Observe the documentation of your configuration program.
After converting the valve system, you need to configure the newly added components.
In the PLC configuration software, adapt the lengths of the input and output data to the valve
system.
Because the data is transferred as a byte string and divided up by the user, the position of the data
in the byte string will shift if an additional module is used. However, if you add a module at the left
end of the I/O modules, with an output module, only the parameter byte for the bus module will be
shifted. With an input module, only the diagnostic data will be shifted.
After converting the valve system, always make sure the input and output bytes are still correctly
assigned.
If you have exchanged components without changing their order, you do not need to reconfigure the
valve system. All components will be recognized by the controller.
For the PLC configuration, proceed as described in section 5 "PLC Configuration of the Valve
System" on page 79.
NOTICE